Product details
Advantages
1. Safety - By reducingchance of harm to personnel.
2. Reliability - By reducing chances of flashover and short circuits that cause damage to equipment and costly outages. A practical example would be the reduction in fault events as a result of wildlife crossing the phases.
3. Protection - Of conductors in industrial facilities with high amounts of trace materials like oils, sawdust, moisture, and caustic materials.
4. Reduced Impedance - From surface corrosion and defects.
Specification
-Current Rating: 400 A to 6300 A(CU) or 100A to 4000A(AL)
-Ingress protection of IP54 or IP65
-Insulation curent rating: [upto 1000 A]
-Standard lengths of 4m/3m/2m/1m
-System Voltage: AC380 /690V
-Conductor material: High conductivity Cu or AL
-Halogen free, fire retardant Class-B-Epoxy insulation
Components
Straight feeder
Feeder Bustrunking
Plug-in Busbar trunking
Joint block
Horizontal Elbow
Horizontal Offset [Z] Elbow
Vertical Elbow
Vertical Offset [Z] Elbow
Vertical Tee Section
Standard Flange End
Flange End Box cum Termination Detail
MCCB Plug-in Boxes
Rated current (A) |
Earthing bar resistance (10-6Ω/m) |
Copper conductor |
AL conductor |
100 |
368.3 |
404.7 |
160 |
368.3 |
404.7 |
200 |
368.3 |
404.7 |
250 |
368.3 |
404.7 |
400 |
248 |
306.8 |
500 |
213.6 |
248.8 |
630 |
213.6 |
210.3 |
800 |
168.2 |
163 |
1000 |
139.5 |
141 |
1250 |
112.3 |
112.5 |
1350 |
96.6 |
101.7 |
1600 |
82.8 |
90.8 |
2000 |
66.5 |
74.8 |
2300 |
54.6 |
66.6 |
2500 |
44.9 |
62.2 |
3150 |
34.5 |
40.2 |
3800 |
29.6 |
33.3 |
4000 |
27.9 |
31.1 |
4500 |
22.5 |
/ |
5000 |
20.5 |
/ |
Application:
Business premises and commercial complexes
Resorts and hotels
Educational institutions
Shopping centres
Assembly lines
Industries
Airports
Hospitals
Oil & gas platforms
Application
If drawings available, please send us the drawing for better quote.